WhatsApp/WeChat/Skype/Phone:+8618625503172
Email:
info@qingzhou-cable.com
Tel:
+8618625503172
Fax:
+8618625503172
Skype:
+8618625503172
50kW hybrid inverter + 50kWh LFP battery + 3-level BMS + EMS + HVAC + FSS in a single IP54 cabinet (780x640x2000mm, ~625kg). Grade A LiFePO4 cells (3.2V/100Ah), 10-module 16S1P, 6,000+ cycles at 90% DOD. Round-trip efficiency >=90%. Three modes: Grid-tied / Off-grid / Hybrid. 380V three-phase, Deye compatible. Factory pre-commissioned. CE, RoHS, ISO9001, IEC 62619, UL 1973. 5-year warranty. Configurable to site.
A compact 50kW/50kWh all-in-one BESS cabinet integrating a hybrid inverter, high-voltage LFP battery rack (10 modules, 16S1P), 3-level BMS, EMS, HVAC, and fire suppression system in a single IP54 enclosure (780×640×2000mm, ~625kg). Engineered for peak shaving, backup power, solar self-consumption, TOU arbitrage, and microgrid applications. Every system is configured to site requirements — capacity, operating mode, and protection design confirmed per project.
• AC Power: 50kW — Three-Phase 380V AC 50/60Hz
• Nominal Energy: 50kWh — 10 Modules 16S1P LFP
• Battery Cells: Grade A LiFePO4 — 3.2V / 100Ah
• Cycle Life: 6,000+ at 25°C, 0.5C, 90% DOD
• Architecture: All-in-One — BESS + BMS + EMS + HVAC + FSS
• Round-Trip Efficiency: ≥90% System-Level
• Enclosure: IP54 — 780×640×2000mm — ~625kg
• BMS: 3-Level: Cell / Pack / System
• Certifications: CE / RoHS / ISO9001 / ISO14001
• Warranty: 5 Years Standard
6,000+ Cycle Longevity:Grade A LiFePO4 cells rated for 6,000+ cycles at 90% DOD — equivalent to 15+ years in daily-cycling applications. LFP chemistry with >270 °C thermal runaway temperature and zero cobalt delivers the lowest total cost of ownership in the C&I storage class.
High-Rate Energy Throughput:50kW continuous AC output with ≥90% round-trip efficiency — maximizing revenue per kWh in peak-shaving and TOU arbitrage applications. 0.5C charge/discharge capability ensures rapid response to grid signals and load changes.
3-Level Smart Protection:Comprehensive safety architecture: Level 1 — cell-level voltage/temperature/IR monitoring; Level 2 — pack-level SOC/SOH estimation and fault isolation; Level 3 — system-level EMS coordination, HVAC interlock, and auto-extinguishing FSS. 24/7 protection without external water or gas supply.
Category | Parameter | Specification |
General System | System Configuration | 50kW / 50kWh AC-Coupled, Three-Phase All-in-One Cabinet |
Application | C&I Peak Shaving, Backup Power, Microgrid, Solar Self-Consumption, TOU Arbitrage | |
Ingress Protection | IP54 — Outdoor-Grade Installation | |
Battery System | Cell Specification | LiFePO4 (LFP) Grade A — 3.2V / 100Ah Prismatic |
Nominal Energy | 50 kWh — 10 Modules, 16S1P Configuration | |
Cycle Life | ≥ 6,000 Cycles at 25°C, 0.5C, 90% DOD | |
Round-Trip Efficiency | ≥ 90% System-Level | |
Hybrid Inverter | Rated Power | 50kW — Deye or Equivalent High-Performance Platform |
Grid Type | Three-Phase 4-Wire (3P+N+PE) — 380V AC | |
Frequency | 50 Hz / 60 Hz | |
Safety & Mechanical | BMS Architecture | 3-Level — Cell / Pack / System with HVAC Interlock & Auto-Extinguishing FSS |
Dimensions (W×D×H) | 780 × 640 × 2000 mm | |
System Weight | Approx. 625 kg — Fully Loaded | |
Operating Temperature | -20 °C to +55 °C — HVAC-Controlled Internal Environment | |
Table 1.0 — GCB-E50 technical specifications. All parameters reference values; final configuration confirmed per project. IEC 62619 / UL 1973 cell certifications. Customization available subject to project volume.
Frequently Asked Questions
Q: What is the expected payback period for a GCB-E50 in a peak-shaving application?
Payback depends on the local tariff structure — specifically the peak-to-off-peak price spread and demand charge rate. In markets with demand charges above $10/kW/month and peak rates 2–3× off-peak, typical payback is 3–5 years. The 6,000+ cycle life at 90% DOD ensures the system remains economically productive for 15+ years before significant capacity fade. We can model your specific tariff and load profile for a project-specific ROI analysis.
Q: Can the GCB-E50 operate fully off-grid with solar?
Yes. The GCB-E50's hybrid inverter supports grid-tied, off-grid, and hybrid (solar-plus-storage with grid-fallback) modes. In off-grid configuration, the system powers critical loads with seamless transfer — no interruption during grid outage. Solar PV can be AC-coupled through the inverter. The applicable mode, solar array sizing, and protection coordination must be validated for your specific site and local grid code. All modes are configurable — not locked to a single topology.
Q: What customization options are available for the GCB-E50?
The GCB-E50 is fully configurable to project requirements. Customization options subject to project volume include: inverter platform selection (Deye or equivalent), cabinet color and OEM branding (logo + housing), communication protocol (Modbus TCP/RTU, CAN, IEC 61850), cell capacity selection, and destination-market certification packages. Contact us with your project specification for a customized proposal — engineering response within 2–3 business days.
Q: What site preparations are needed before GCB-E50 installation?
Pre-installation requirements: (1) Level concrete pad or indoor floor with adequate load-bearing (~650kg + safety factor), (2) Minimum clearances — 1m front and rear for service access per local electrical code, (3) AC cable routing from the main distribution panel to the cabinet location, (4) Communication — Ethernet cable for remote monitoring (4G optional), (5) Environmental — ambient temperature within -20 to +55 °C, protected from direct flooding. We provides a detailed site preparation guide and remote commissioning support. On-site engineer available for projects above 500 kWh.