Aluminum or Copper Conductor.
EPR Insulation.
Bare Copper Concentric Neutrals.
Low Density Polyethylene Jacket.
Concentric Cable
APPLICATIONS
Predominantly used for primary underground distribution in conduit systems; suitable for use in wet or dry locations, direct
burial, underground duct, and where exposed to sunlight. To be used at 15,000 volts or less and at conductor
temperatures not to exceed 105°C for normal operation.
SPECIFICATIONS
15kV Primary UD EPR Cable meets or exceeds the following ASTM specifications:
• B3 Soft Annealed Copper Wire
• B8 Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard or Soft
• B230 Aluminum, 1350-H19 Wire for Electrical Purposes
• B231 Aluminum 1350 Conductors, Concentric-Lay-Stranded
• B609 Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
• ANSI/ICEA S-94-649
• AEIC CS-8
• UL 1072, When Specified
• RUS 1728F-U1
• ANSI/ICEA S-94-649
• AEIC CS-8
• UL 1072, When Specified
• RUS 1728F-U1
CONSTRUCTION
The cable is composed of a solid or moisture blocked reverse lay, compressed stranded soft drawn copper, or a solid or moisture blocked reverse lay or unilay compressed stranded 1350-H16/26 aluminum phase conductor, covered by a semi-conducting cross-linked polyethylene strand shield, an ethylene propylene rubber primary insulation, and a semiconducting cross-linked polyethylene insulation shield. Conductors are available with either 100% or 133% insulation levels. A concentric neutral of bare copper wires and a sunlight resistant, -40°C rated, insulating linear low density polyethylene jacket are applied over the insulation shield. The cable is identified by surface print on the jacket and with the lightning bolt symbol for supply cables indented in the jacket. Red extruded stripes available upon request. A semiconducting polyethylene jacket is also available upon request.
Phase Conductor |
Neutral |
Thickness Per Cond. (mils) |
Diameter (mils) | Weight 1000 feet (lbs.) | Allowable Ampacities+ | ||||||||
Size (AWG or kcmil) |
Strand- ing |
No. of Wires |
Size (AWG) |
Nominal Insul. | Insul. Shield min. Point |
Approx. Jkt. | Bare Phase Cond. |
Over Insul. | Over Insul. Shield |
Comp. Cable |
Comp. Cable |
Direct Burial |
In Ducts |
ALUMINUM CONDUCTOR - 100% INSULATION LEVEL | |||||||||||||
2 | Solid | 10 | 14 | 175 | 30 | 50 | 258 | 653 | 733 | 961 | 485 | 168* | 119* |
2 | 7 | 10 | 14 | 175 | 30 | 50 | 283 | 678 | 758 | 986 | 504 | 168* | 119* |
1 | Solid | 13 | 14 | 175 | 30 | 50 | 289 | 685 | 765 | 993 | 555 | 193* | 137* |
1 | 19 | 13 | 14 | 175 | 30 | 50 | 322 | 718 | 798 | 1026 | 577 | 193* | 137* |
1/0 | Solid | 16 | 14 | 175 | 30 | 50 | 325 | 720 | 800 | 1028 | 629 | 218* | 155* |
1/0 | 19 | 16 | 14 | 175 | 30 | 50 | 352 | 748 | 828 | 1056 | 648 | 218* | 155* |
2/0 | 19 | 20 | 14 | 175 | 30 | 50 | 395 | 790 | 870 | 1098 | 745 | 248* | 177* |
3/0 | 19 | 25 | 14 | 175 | 30 | 50 | 443 | 838 | 918 | 1146 | 862 | 284* | 201* |
4/0 | 19 | 20 | 12 | 175 | 30 | 50 | 498 | 893 | 973 | 1234 | 1042 | 324* | 230* |
250 | 37 | 16 | 10 | 175 | 30 | 50 | 558 | 963 | 1043 | 1346 | 1268 | 360* | 257* |
350 | 37 | 18 | 14 | 175 | 40 | 50 | 661 | 1068 | 1168 | 1396 | 1118 | 389** | 319** |
500 | 37 | 25 | 14 | 175 | 40 | 50 | 789 | 1193 | 1293 | 1521 | 1419 | 468** | 384** |
750 | 61 | 24 | 12 | 175 | 40 | 80 | 968 | 1383 | 1483 | 1798 | 2030 | 569** | 468** |
1000 | 61 | 20 | 10 | 175 | 40 | 80 | 1117 | 1530 | 1630 | 1988 | 2567 | 642** | 542** |
1250 | 91 | 25 | 10 | 220 | 55 | 80 | 1250 | 1765 | 1895 | 2253 | 3278 | 688** | 604** |
1500 | 91 | 30 | 10 | 220 | 55 | 80 | 1370 | 1885 | 2015 | 2373 | 3762 | 726** | 637** |
COPPER CONDUCTOR - 100% INSULATION LEVEL | |||||||||||||
2 | Solid | 16 | 14 | 175 | 30 | 50 | 258 | 653 | 733 | 961 | 697 | 210* | 150* |
2 | 7 | 16 | 14 | 175 | 30 | 50 | 283 | 678 | 758 | 986 | 719 | 210* | 150* |
1 | Solid | 20 | 14 | 175 | 30 | 50 | 289 | 685 | 765 | 993 | 815 | 240* | 171* |
1 | 19 | 20 | 14 | 175 | 30 | 50 | 322 | 718 | 798 | 1026 | 841 | 240* | 171* |
1/0 | Solid | 25 | 14 | 175 | 30 | 50 | 325 | 720 | 800 | 1028 | 959 | 273* | 194* |
1/0 | 19 | 25 | 14 | 175 | 30 | 50 | 362 | 758 | 838 | 1066 | 991 | 273* | 194* |
2/0 | 19 | 20 | 12 | 175 | 30 | 50 | 405 | 800 | 880 | 1142 | 1204 | 313* | 224* |
3/0 | 19 | 25 | 12 | 175 | 30 | 50 | 456 | 853 | 933 | 1194 | 1437 | 358* | 255* |
4/0 | 19 | 20 | 10 | 175 | 30 | 50 | 512 | 908 | 988 | 1291 | 1768 | 410* | 293* |
250 | 37 | 24 | 10 | 175 | 30 | 50 | 558 | 963 | 1043 | 1346 | 2047 | 446* | 322* |
350 | 37 | 18 | 12 | 175 | 40 | 50 | 661 | 1068 | 1168 | 1429 | 2027 | 489** | 400** |
500 | 37 | 26 | 12 | 175 | 40 | 50 | 789 | 1193 | 1293 | 1554 | 2722 | 577** | 472** |
750 | 61 | 25 | 10 | 175 | 40 | 80 | 968 | 1383 | 1483 | 1840 | 3990 | 649** | 532** |
1000 | 61 | 26 | 9 | 175 | 40 | 80 | 1117 | 1530 | 1630 | 2013 | 5136 | 720** | 630** |
1250 | 91 | 26 | 8 | 220 | 55 | 80 | 1250 | 1765 | 1895 | 2306 | 6535 | 760** | 667** |
+ Ampacities shown assume use of 100% load factor, 60 Hz current, 36" burial depth, 20°C ambient temperature, 90°C conductor temperature, earth RHO 90, insulation and shield RHO 400 * Full neutral construction (Ampacities assume - single phase circuit, one cable) ** 1/3 neutral cable (Ampacities assume - three phase circuit, 3 cables triplexed, multi-point grounding per ICEA methods) |
Phase Conductor |
Neutral | Thickness Per Cond. (mils) | Nominal Diameter (mils) | Weight 1000 feet (lbs.) | Allowable Ampacities+ | ||||||||
Size (AWG or kcmil) |
Strand- ing |
No. of Wires |
Size (AWG) |
Nominal Insul. | Insul. Shield min. Point |
Approx. Jkt. |
Bare Phase Cond. |
Over Insul. |
Over Insul. Shield |
Comp. Cable |
Comp. Cable |
Direct Burial |
In Ducts |
ALUMINUM CONDUCTOR - 0.220" INSULATION - 133% INSULATION LEVEL | |||||||||||||
2 | Solid | 10 | 14 | 220 | 30 | 50 | 258 | 745 | 825 | 1053 | 556 | 168* | 119* |
2 | 7 | 10 | 14 | 220 | 30 | 50 | 283 | 770 | 850 | 1078 | 577 | 168* | 119* |
1 | Solid | 13 | 14 | 220 | 30 | 50 | 289 | 778 | 858 | 1086 | 628 | 193* | 137* |
1 | 19 | 13 | 14 | 220 | 30 | 50 | 322 | 810 | 890 | 1118 | 652 | 193* | 137* |
1/0 | Solid | 16 | 14 | 220 | 30 | 50 | 325 | 813 | 893 | 1121 | 705 | 218* | 155* |
1/0 | 19 | 16 | 14 | 220 | 30 | 50 | 352 | 840 | 920 | 1148 | 726 | 218* | 155* |
2/0 | 19 | 20 | 14 | 220 | 30 | 50 | 395 | 883 | 963 | 1191 | 826 | 248* | 177* |
3/0 | 19 | 25 | 14 | 220 | 30 | 50 | 443 | 930 | 1010 | 1238 | 947 | 284* | 201* |
4/0 | 19 | 20 | 12 | 220 | 30 | 50 | 498 | 985 | 1065 | 1327 | 1133 | 324* | 230* |
250 | 37 | 16 | 10 | 220 | 40 | 50 | 558 | 1055 | 1155 | 1459 | 1389 | 360* | 257* |
350 | 37 | 18 | 14 | 220 | 40 | 50 | 661 | 1158 | 1258 | 1486 | 1219 | 389** | 319** |
500 | 37 | 25 | 14 | 220 | 40 | 50 | 789 | 1285 | 1385 | 1613 | 1532 | 468** | 384** |
750 | 61 | 24 | 12 | 220 | 40 | 80 | 968 | 1475 | 1575 | 1891 | 2162 | 569** | 468** |
1000 | 61 | 20 | 10 | 220 | 55 | 80 | 1117 | 1623 | 1753 | 2110 | 2762 | 642** | 542** |
1250 | 91 | 25 | 10 | 220 | 55 | 80 | 1250 | 1765 | 1895 | 2253 | 3278 | 688** | 604** |
1500 | 91 | 30 | 10 | 220 | 55 | 80 | 1370 | 1885 | 2015 | 2373 | 3762 | 726** | 637** |
COPPER CONDUCTOR - 0.220" INSULATION - 133% INSULATION LEVEL | |||||||||||||
2 | Solid | 16 | 14 | 220 | 30 | 50 | 258 | 745 | 825 | 1053 | 768 | 210* | 150* |
2 | 7 | 16 | 14 | 220 | 30 | 50 | 283 | 770 | 850 | 1078 | 792 | 210* | 150* |
1 | Solid | 20 | 14 | 220 | 30 | 50 | 289 | 778 | 858 | 1086 | 888 | 240* | 171* |
1 | 19 | 20 | 14 | 220 | 30 | 50 | 322 | 810 | 890 | 1118 | 916 | 240* | 171* |
1/0 | Solid | 25 | 14 | 220 | 30 | 50 | 325 | 813 | 893 | 1121 | 1035 | 273* | 194* |
1/0 | 19 | 25 | 14 | 220 | 30 | 50 | 362 | 850 | 930 | 1158 | 1070 | 273* | 194* |
2/0 | 19 | 20 | 12 | 220 | 30 | 50 | 405 | 893 | 973 | 1234 | 1288 | 313* | 224* |
3/0 | 19 | 25 | 12 | 220 | 30 | 50 | 456 | 943 | 1023 | 1284 | 1523 | 358* | 255* |
4/0 | 19 | 20 | 10 | 220 | 30 | 50 | 512 | 1000 | 1080 | 1384 | 1863 | 410* | 293* |
250 | 37 | 24 | 10 | 220 | 40 | 50 | 558 | 1055 | 1155 | 1459 | 2168 | 446* | 322* |
350 | 37 | 18 | 12 | 220 | 40 | 50 | 661 | 1158 | 1258 | 1519 | 2130 | 489** | 400** |
500 | 37 | 26 | 12 | 220 | 40 | 50 | 789 | 1285 | 1385 | 1647 | 2837 | 577** | 472** |
750 | 61 | 25 | 10 | 220 | 40 | 80 | 968 | 1475 | 1575 | 1933 | 4125 | 649** | 532** |
1000 | 61 | 26 | 9 | 220 | 55 | 80 | 1117 | 1623 | 1753 | 2135 | 5332 | 720** | 630** |
1250 | 91 | 26 | 8 | 220 | 55 | 80 | 1250 | 1765 | 1895 | 2306 | 6535 | 760** | 667** |
+ Ampacities shown assume use of 100% load factor, 60 Hz current, 36" burial depth, 20°C ambient temperature, 90°C conductor temperature, earth RHO 90, insulation and shield RHO 400 * Full neutral construction (Ampacities assume - single phase circuit, one cable ** 1/3 neutral cable (Ampacities assume - three phase circuit, 3 cables triplexed, multi-point grounding per ICEA methods) |