Cable Electrical Armoured and Non Armoured for Russia

Date:2025-04-14

Cable Electrical Armoured and Non Armoured for Russia

What kind of Cables Elecrical Power Can We Provide?


Description
CBL ELEC ARM,0.6/1KV,4CX150MM²
Cable, Electrical, Armoured

Voltage                        0.6 / 1 kV
Construction                   Cu/XLPE/SHF1/SWA/SHF1
Identification, cores          #NAME?
                               BROWN(L1), BLACK(L2), GREY(L3)
Number, cores                  4
Cross section, cores           150 mm²
Diameter, od, overall          NOTE LESS 52.1 MM (MIN)
                               59.4 MM (MAX)

Mat, insulation                XLPE
Mat, armour bending            SHF1
Mat, armour                    GSWA
Diameter, under armour         40.1 mm (MIN)
                               49.9 mm (MAX)
Number of wire                 53
Diameter, wire                 2.5 mm
Color, sheath                  BLACK
Weigh                          9100 kgs/km
Bending radius                 476 mm
Resistance, conductor          0.124 ohm/km AT 20 °C
Reactance                      0.074 ohm/km AT 50 Hz
Current rating, air            399 A AT 30 °C (ADMISSIBLE
                               SUSTAINED)
                               287 A AT 20 °C (DIRECTLY
                               BURIED)
Temperature rating, conductor  90 / 250 °C
Climate application            HL/UHL 1 GOST 15150
Temperature rating , ambient   -50 / +50 °C
Relative humidity              95 %  AT 25 °C
Installation temperature       -30 °C (WITHOUT PRE-HEATING)
Service life                   30 YR (MIN)
Warranty rated life            5 YR
Size, glanding                 25
Bedding diameter range         18.2 TO 26.2 mm
Armor range                    0.4 TO 1.6 mm (GSWA)
Compliance with regulatory
requirements                   IEC 60502-1/GOST 31996
                               IEC 61034-2/GOST IEC 61034-2
                               (MINIMUM LIGHT TRANSMISSION
                               VALUE OF 60%)
                               IEC 60754-1 /GOST IEC 60754-1
                               (MAXIMUM HALOGEN GAS EMISSION
                               OF 0.5%)
IEC 60754-2 / GOST IEC 60754-2(index pH ≥ 4.3,
conductivity ≤ 10 μS.mm-1)
IEC 60684-2 (maximum fluorine emission 0.1%)
IEC 60332-3-22 / ГОСТ IEC 60332-3-22(flame retardant
cable, category A)
IEC 60079-14 / GOST IEC 60079-14 and GOST R 58342
(for cable use in hazardous classified areas)
Notes:
1. Any deviations from the stated requirements must be
communicated to the Customer and agreed.
2. Cable fillers shall be solid, non-hygroscopic and fill
the cross-section such that the transmission of gas or
hydrocarbons along the length of the cable, under pressure,
is not possible
3. Installation Method E (МЭК60364-5-52 / GOST R 50571-5-52)
for Three loaded conductors in air, at 30 C
4. Installation Method D2 (МЭК60364-5-52 /GOST R 50571-5-52)
for Sheathed Single core or Multi core cables directly
buried in the ground, at 20 C, thermal resistivity
1.5 Km/W, depth of laying 0.7m
5. Maximum drum diameter, 2 m
6.Minimum radius of the cable drum core, 250 mm
7.This cable can be used with cable gland triton,
manufacturer CMP.
Compliance internal requirements of company Sakhalin Energy:
1000-S-40-68-S-0003-00 Technical specification for
electric cable  / wires & glands onshore
Outer sheath shall be highly resistant to mud, ultra-violet
radiation and airborne contaminants associated with
petrochemical installations.
Mat, insulation                XLPE
Mat, armour bending            SHF1
Mat, armour                    GSWA
Diameter, under armour         40.1 mm (MIN)
                               49.9 mm (MAX)
Number of wire                 53
Diameter, wire                 2.5 mm
Color, sheath                  BLACK
Weigh                          9100 kgs/km
Bending radius                 476 mm
Resistance, conductor          0.124 ohm/km AT 20 °C
Reactance                      0.074 ohm/km AT 50 Hz
Current rating, air            399 A AT 30 °C (ADMISSIBLE
                               SUSTAINED)
                               287 A AT 20 °C (DIRECTLY
                               BURIED)
Temperature rating, conductor  90 / 250 °C
Climate application            HL/UHL 1 GOST 15150
Temperature rating , ambient   -50 / +50 °C
Relative humidity              95 %  AT 25 °C
Installation temperature       -30 °C (WITHOUT PRE-HEATING)
Service life                   30 YR (MIN)
Warranty rated life            5 YR
Size, glanding                 25
Bedding diameter range         18.2 TO 26.2 mm
Armor range                    0.4 TO 1.6 mm (GSWA)
Compliance with regulatory
requirements                   IEC 60502-1/GOST 31996
                               IEC 61034-2/GOST IEC 61034-2
                               (MINIMUM LIGHT TRANSMISSION
                               VALUE OF 60%)
                               IEC 60754-1 /GOST IEC 60754-1
                               (MAXIMUM HALOGEN GAS EMISSION
                               OF 0.5%)
IEC 60754-2 / GOST IEC 60754-2(index pH ≥ 4.3,
conductivity ≤ 10 μS.mm-1)
IEC 60684-2 (maximum fluorine emission 0.1%)
IEC 60332-3-22 / ГОСТ IEC 60332-3-22(flame retardant
cable, category A)
IEC 60079-14 / GOST IEC 60079-14 and GOST R 58342
(for cable use in hazardous classified areas)
Notes:
1. Any deviations from the stated requirements must be
communicated to the Customer and agreed.
2. Cable fillers shall be solid, non-hygroscopic and fill
the cross-section such that the transmission of gas or
hydrocarbons along the length of the cable, under pressure,
is not possible
3. Installation Method E (МЭК60364-5-52 / GOST R 50571-5-52)
for Three loaded conductors in air, at 30 C
4. Installation Method D2 (МЭК60364-5-52 /GOST R 50571-5-52)
for Sheathed Single core or Multi core cables directly
buried in the ground, at 20 C, thermal resistivity
1.5 Km/W, depth of laying 0.7m
5. Maximum drum diameter, 2 m
6.Minimum radius of the cable drum core, 250 mm
7.This cable can be used with cable gland triton,
manufacturer CMP.
Compliance internal requirements of company Sakhalin Energy:
1000-S-40-68-S-0003-00 Technical specification for
electric cable  / wires & glands onshore
Outer sheath shall be highly resistant to mud, ultra-violet
radiation and airborne contaminants associated with
petrochemical installations.

VENDOR DOCUMENT REQUIREMENTS:
A01 Vendor Master Data Schedule (VMDS)
H18 Catalogue Data
K03 Performance Test Results
K38 CU TR Certificate , Declaration of Conformity for Low Voltage Equipment
K39 RF , CU TR Fire Safety Certificate of Conformity
L04 Quality Management Accreditation (including any manufacturing licenses held by Vendor, e.g. API, ASME etc.)
P06 Preparation for Shipping with Recommended Handling, Storage & Preservation Procedures
CBL ELEC N-ARM,CU,PVC,1X6MM²,BL
Cable, Electrical, Non armoured

Voltage                        0.45 / 0.75 kV
Mat, conductor                 COPPER
Mat spec, insulation           PVC
Colour, outer sheath           BLUE
Number, cores                  1
Cross section, cores           6 mm²
Diameter, od, overall          6.5 mm

Shape, conductor               CIRCULAR
Class                          5 (BS EN 60228 / GOST 22483)
Mat, outer sheath              PVC
Dia, overall                   6.5 mm
Weight                         85 kg/km
Bending radius no more 5XD     32.5 mm (APPROXIMATE)
Resistance, conductor dc       3.08 ohm/km AT 20 °C
                               (IEC 60228/GOST 22483)
Current, admissible
sustained in air               48 A(AT 30 °C)
Current, admissible
sustained directly buried      41 A (AT 20 °C)
Temp, conductor                160 °C (IN SHORT-CIRCUIT)
                               CLIMATE APPLICATION
                               GOST 15150
Temp range, ambient            -50 TO +50 °C
Humidity, relative  at 25 °C   95%
Temperature, installation      -15 °C WITHOUT PRE-HEATING
Service life                   30 YR
The outer sheath of cable shall be an extruded layer of
shf1 or any other thermoplastic pvc, intrinsically flame
retardant, low smoke, oil and uv resistant and antitermite
protected that is suitable for the cold
operating temperature
Compliance internal requirements of company sakhalin
energy:
1. 1000-S-40-68-S-0003-00 technical specification
for electric cables / wires & glands onshore
Compliance with regulatory requirements:
1.IEC 60227-1 / GOST IEC 60227-1 (OR GOST 31947 AS
agreed with the customer)
2.IEC 61034-2 / GOST IEC 61034-2 (minimum light
transmission value of 60%)
3.IEC 60754-1 / GOST IEC 60754-1 (maximum halogen
gas emission of 0.5%)
4.IEC 60754-2 / GOST IEC 60754-2 (index PH >= 4.3,
conductivity <=10 ΜS.MM-1)
5.IEC 60684-2 (maximum fluorine emission 0.1%)
6.IEC 60332-3-22 / ГОСТ IEC 60332-3-22(flame
retardant cable, category A)
NOTES:
1. Any deviations from the stated requirements must be
communicated to the customer and agreed.
2. Installation method e (МЭК60364-5-52 / GOST R 50571-5-52)
for three loaded conductors in air
3. Installation method d2 (МЭК60364-5-52 / GOSTR50571-5-52)
for sheathed single core or multi core cables directly
buried in the ground, at 20 °C, thermal resistivity 1.5
KxM/W, DEPTH OF LAYING 0.7 m
4. Maximum drum diameter, m 2
minimum radius of the cable drum core, mm 100
Shape, conductor               CIRCULAR
Class                          5 (BS EN 60228 / GOST 22483)
Mat, outer sheath              PVC
Dia, overall                   6.5 mm
Weight                         85 kg/km
Bending radius no more 5XD     32.5 mm (APPROXIMATE)
Resistance, conductor dc       3.08 ohm/km AT 20 °C
                               (IEC 60228/GOST 22483)
Current, admissible
sustained in air               48 A(AT 30 °C)
Current, admissible
sustained directly buried      41 A (AT 20 °C)
Temp, conductor                160 °C (IN SHORT-CIRCUIT)
                               CLIMATE APPLICATION
                               GOST 15150
Temp range, ambient            -50 TO +50 °C
Humidity, relative  at 25 °C   95%
Temperature, installation      -15 °C WITHOUT PRE-HEATING
Service life                   30 YR
The outer sheath of cable shall be an extruded layer of
shf1 or any other thermoplastic pvc, intrinsically flame
retardant, low smoke, oil and uv resistant and antitermite
protected that is suitable for the cold
operating temperature
Compliance internal requirements of company sakhalin
energy:
1. 1000-S-40-68-S-0003-00 technical specification
for electric cables / wires & glands onshore
Compliance with regulatory requirements:
1.IEC 60227-1 / GOST IEC 60227-1 (OR GOST 31947 AS
agreed with the customer)
2.IEC 61034-2 / GOST IEC 61034-2 (minimum light
transmission value of 60%)
3.IEC 60754-1 / GOST IEC 60754-1 (maximum halogen
gas emission of 0.5%)
4.IEC 60754-2 / GOST IEC 60754-2 (index PH >= 4.3,
conductivity <=10 ΜS.MM-1)
5.IEC 60684-2 (maximum fluorine emission 0.1%)
6.IEC 60332-3-22 / ГОСТ IEC 60332-3-22(flame
retardant cable, category A)
NOTES:
1. Any deviations from the stated requirements must be
communicated to the customer and agreed.
2. Installation method e (МЭК60364-5-52 / GOST R 50571-5-52)
for three loaded conductors in air
3. Installation method d2 (МЭК60364-5-52 / GOSTR50571-5-52)
for sheathed single core or multi core cables directly
buried in the ground, at 20 °C, thermal resistivity 1.5
KxM/W, DEPTH OF LAYING 0.7 m
4. Maximum drum diameter, m 2
minimum radius of the cable drum core, mm 100

Recommended for purchase in Russian Federation

VENDOR DOCUMENT REQUIREMENTS:
A01 Vendor Master Data Schedule (VMDS)
H18 Catalogue Data
K03 Performance Test Results
K38 CU TR Certificate , Declaration of Conformity for Low Voltage Equipment
K39 RF , CU TR Fire Safety Certificate of Conformity
L04 Quality Management Accreditation (including any manufacturing licenses held by Vendor, e.g. API, ASME etc.)
P06 Preparation for Shipping with Recommended Handling, Storage & Preservation Procedures
CBL ELEC N-ARM FIRE,0.75KV,1X4MM²,BLK
Fire spec non armoured electrical cable

Flammability properties        FLAME RETANDANT
Voltage                        0.45/0.75 kV
Construction                   Cu/LSHF
Mat, conductor wire            UNCOATED ANNEALED COPPER
Mat spec, insulation           LSHF
Identification, cores          BLACK
Number, cores                  1
Cross section, cores           4 mm²
Diameter, od, overall          3.9 TO 4.8 mm

Frequency, nominal             UP TO 400 Hz
Shape                          CIRCULAR
Class                          5
Standard                       IEC 60228/GOST 22483
Resistance, conductor DC, max  4.95 ohm/km AT 20 °C
Reactance, approx              0.098 ohm/km AT 50 Hz
Current rating, short-circuit  1.36/0.61/0.43 kA
(0.1/0.5/1.0 s)
Temperature rating, conductor  70 °C (OPERATING)
160 °C (SHORT CIRCUIT)
Test voltage                   2500 Vac
Temperature range , ambient    -50 TO +50 °C
Tensile strength               9.0 N/mm² (NOT LESS THAN)
Bending radius                 8 x D (MIN)
Relative humidity              98% AT 35 °C
Installation temperature       -15 °C (WITHOUT PRE-HEATING)
Nominal tensile load           14.7 N
Weight, approximate            50 kgs/km
Service life                   20 YR (MIN)
Warranty rated life            3 YR (MIN)
Current rating                 34 А (IEC 60364-5-52 /
GOST R 50571-5-52)
Fire safety requirements:
1. Fire hazard category (cable marking) А
2. The toxicity index of combustion products > 40 g/m³
2. Smoke Density (minimum light transmission) > 60%
Resistance to external factors:
Climatic modification and placement category
HL/UHL 1 GOST 15150
By agreement with the customer, it is allowed to change the
climatic  modification and placement category depending on
the laying conditions
Resistance to alternating bending deformations, cycles
(movements), not less than
Operation requirements:
1. Place of operation:
Onshore technological complexes the cables in all respects,
be suitable for operation in conditions prevailing within a
typical petrochemical facility and the stated service
conditions where the atmosphere shall be regarded as
saliferous and corrosive, as commonly encountered in
installations in close proximity to the
2. Appointment:
The wires are intended for distribution of electric energy
in the electric installations at stationary laying in
lighting and power electric networks as well as for
installation of electrical equipment, machines, tools and
other machines, indoor electric settings
Compliance with regulatory requirements:
1. IEC 60227-3 / GOST IEC 60227-3 or GOST 31947
(Requirements for the construction, size and testing)
2. IEC 60332 - 3-22/  GOST IEC 60332-3-22 (flame spread test
on bunched cables)
3. EN 50305/GOST 12.1.044 (Checking the toxicity index of
combustion products)
4. IEC 61034-2/  GOST IEC 61034-2 (Smoke emission test)
5. The tests at low temperature shall be done in accordance
with IEC 60811-506 for cold impact and IEC 60811-504 for
cold bending or IEC 60811-505 for elongation at break when
the cable is not subjected to bending test.
The tests shall be carried out at a test temperature of (-45
+/- 2) °C for the cold bending and at (-40 +/- 2) °C for the
cold impact test.
Notes:
1. Any deviations from the stated requirements must be
communicated to the Customer and agreed.
2. Manufacturer shall list in his quotation the type tests
and routine tests to which his cables are Subjected
Abbreviations:
1. Cu - сopper
2. LSHF - extruded layer of halogen free low smoke
thermoplastic compound based on polymer compositions
Type tests:
Tests made before supplying, on a general commercial basis,
a type of cable covered by this standard, in order to
demonstrate satisfactory performance characteristics to meet
the intended application
Routine tests:
Tests made by the manufacturer on each manufactured length
of cable to check that each length meets the specified
requirements
Frequency, nominal             UP TO 400 Hz
Shape                          CIRCULAR
Class                          5
Standard                       IEC 60228/GOST 22483
Resistance, conductor DC, max  4.95 ohm/km AT 20 °C
Reactance, approx              0.098 ohm/km AT 50 Hz
Current rating, short-circuit  1.36/0.61/0.43 kA
(0.1/0.5/1.0 s)
Temperature rating, conductor  70 °C (OPERATING)
160 °C (SHORT CIRCUIT)
Test voltage                   2500 Vac
Temperature range , ambient    -50 TO +50 °C
Tensile strength               9.0 N/mm² (NOT LESS THAN)
Bending radius                 8 x D (MIN)
Relative humidity              98% AT 35 °C
Installation temperature       -15 °C (WITHOUT PRE-HEATING)
Nominal tensile load           14.7 N
Weight, approximate            50 kgs/km
Service life                   20 YR (MIN)
Warranty rated life            3 YR (MIN)
Current rating                 34 А (IEC 60364-5-52 /
GOST R 50571-5-52)
Fire safety requirements:
1. Fire hazard category (cable marking) А
2. The toxicity index of combustion products > 40 g/m³
2. Smoke Density (minimum light transmission) > 60%
Resistance to external factors:
Climatic modification and placement category
HL/UHL 1 GOST 15150
By agreement with the customer, it is allowed to change the
climatic  modification and placement category depending on
the laying conditions
Resistance to alternating bending deformations, cycles
(movements), not less than
Operation requirements:
1. Place of operation:
Onshore technological complexes the cables in all respects,
be suitable for operation in conditions prevailing within a
typical petrochemical facility and the stated service
conditions where the atmosphere shall be regarded as
saliferous and corrosive, as commonly encountered in
installations in close proximity to the
2. Appointment:
The wires are intended for distribution of electric energy
in the electric installations at stationary laying in
lighting and power electric networks as well as for
installation of electrical equipment, machines, tools and
other machines, indoor electric settings
Compliance with regulatory requirements:
1. IEC 60227-3 / GOST IEC 60227-3 or GOST 31947
(Requirements for the construction, size and testing)
2. IEC 60332 - 3-22/  GOST IEC 60332-3-22 (flame spread test
on bunched cables)
3. EN 50305/GOST 12.1.044 (Checking the toxicity index of
combustion products)
4. IEC 61034-2/  GOST IEC 61034-2 (Smoke emission test)
5. The tests at low temperature shall be done in accordance
with IEC 60811-506 for cold impact and IEC 60811-504 for
cold bending or IEC 60811-505 for elongation at break when
the cable is not subjected to bending test.
The tests shall be carried out at a test temperature of (-45
+/- 2) °C for the cold bending and at (-40 +/- 2) °C for the
cold impact test.
Notes:
1. Any deviations from the stated requirements must be
communicated to the Customer and agreed.
2. Manufacturer shall list in his quotation the type tests
and routine tests to which his cables are Subjected
Abbreviations:
1. Cu - сopper
2. LSHF - extruded layer of halogen free low smoke
thermoplastic compound based on polymer compositions
Type tests:
Tests made before supplying, on a general commercial basis,
a type of cable covered by this standard, in order to
demonstrate satisfactory performance characteristics to meet
the intended application
Routine tests:
Tests made by the manufacturer on each manufactured length
of cable to check that each length meets the specified
requirements

Recommended for purchase in Russian Federation

VENDOR DOCUMENT REQUIREMENTS:
A01 Vendor Master Data Schedule (VMDS)
B07 Vendor's Declaration of Compliance
H18 Catalogue Data
K04 Factory Acceptance Test (FAT) Report
K38 CU TR Certificate , Declaration of Conformity for Low Voltage Equipment
K39 RF , CU TR fire Safety Certificate of Conformity
L04 Quality Management Accreditation eg ISO 9000 (including any manufacturing licenses held by Vendor, e.g. API, ASME etc.)
N01 Installation, Commissioning, Operating & Maintenance Manuals
P06 Preparation for Shipping with Recommended Handling, Storage & Preservation Procedures
CBL ELEC N-ARM FIRE,0.75KV,1X4MM²,BL
Fire spec non armoured electrical cable

Flammability properties        FLAME RETANDANT
Voltage                        0.45/0.75 kV
Construction                   Cu/LSHF
Mat, conductor wire            UNCOATED ANNEALED COPPER
Mat spec, insulation           LSHF
Identification, cores          BLUE
Number, cores                  1
Cross section, cores           4 mm²
Diameter, od, overall          3.9 TO 4.8 mm

Frequency, nominal             UP TO 400 Hz
Shape                          CIRCULAR
Class                          5
Standard                       IEC 60228/GOST 22483
Resistance, conductor DC, max  4.95 ohm/km AT 20 °C
Reactance, approx              0.098 ohm/km AT 50 Hz
Current rating, short-circuit  1.36/0.61/0.43 kA
(0.1/0.5/1.0 s)
Temperature rating, conductor  70 °C (OPERATING)
160 °C (SHORT CIRCUIT)
Test voltage                   2500 Vac
Temperature range , ambient    -50 TO +50 °C
Tensile strength               9.0 N/mm² (NOT LESS THAN)
Bending radius                 8 x D (MIN)
Relative humidity              98% AT 35 °C
Installation temperature       -15 °C (WITHOUT PRE-HEATING)
Nominal tensile load           14.7 N
Weight, approximate            50 kgs/km
Service life                   20 YR (MIN)
Warranty rated life            3 YR (MIN)
Current rating                 34 А (IEC 60364-5-52 /
GOST R 50571-5-52)
Fire safety requirements:
1. Fire hazard category (cable marking) А
2. The toxicity index of combustion products > 40 g/m³
2. Smoke Density (minimum light transmission) > 60%
Resistance to external factors:
Climatic modification and placement category
HL/UHL 1 GOST 15150
By agreement with the customer, it is allowed to change the
climatic  modification and placement category depending on
the laying conditions
Resistance to alternating bending deformations, cycles
(movements), not less than
Operation requirements:
1. Place of operation:
Onshore technological complexes the cables in all respects,
be suitable for operation in conditions prevailing within a
typical petrochemical facility and the stated service
conditions where the atmosphere shall be regarded as
saliferous and corrosive, as commonly encountered in
installations in close proximity to the
2. Appointment:
The wires are intended for distribution of electric energy
in the electric installations at stationary laying in
lighting and power electric networks as well as for
installation of electrical equipment, machines, tools and
other machines, indoor electric settings
Compliance with regulatory requirements:
1. IEC 60227-3 / GOST IEC 60227-3 or GOST 31947
(Requirements for the construction, size and testing)
2. IEC 60332 - 3-22/  GOST IEC 60332-3-22 (flame spread test
on bunched cables)
3. EN 50305/GOST 12.1.044 (Checking the toxicity index of
combustion products)
4. IEC 61034-2/  GOST IEC 61034-2 (Smoke emission test)
5. The tests at low temperature shall be done in accordance
with IEC 60811-506 for cold impact and IEC 60811-504 for
cold bending or IEC 60811-505 for elongation at break when
the cable is not subjected to bending test.
The tests shall be carried out at a test temperature of (-45
+/- 2) °C for the cold bending and at (-40 +/- 2) °C for the
cold impact test.
Notes:
1. Any deviations from the stated requirements must be
communicated to the Customer and agreed.
2. Manufacturer shall list in his quotation the type tests
and routine tests to which his cables are Subjected
Abbreviations:
1. Cu - сopper
2. LSHF - extruded layer of halogen free low smoke
thermoplastic compound based on polymer compositions
Type tests:
Tests made before supplying, on a general commercial basis,
a type of cable covered by this standard, in order to
demonstrate satisfactory performance characteristics to meet
the intended application
Routine tests:
Tests made by the manufacturer on each manufactured length
of cable to check that each length meets the specified
requirements
Frequency, nominal             UP TO 400 Hz
Shape                          CIRCULAR
Class                          5
Standard                       IEC 60228/GOST 22483
Resistance, conductor DC, max  4.95 ohm/km AT 20 °C
Reactance, approx              0.098 ohm/km AT 50 Hz
Current rating, short-circuit  1.36/0.61/0.43 kA
(0.1/0.5/1.0 s)
Temperature rating, conductor  70 °C (OPERATING)
160 °C (SHORT CIRCUIT)
Test voltage                   2500 Vac
Temperature range , ambient    -50 TO +50 °C
Tensile strength               9.0 N/mm² (NOT LESS THAN)
Bending radius                 8 x D (MIN)
Relative humidity              98% AT 35 °C
Installation temperature       -15 °C (WITHOUT PRE-HEATING)
Nominal tensile load           14.7 N
Weight, approximate            50 kgs/km
Service life                   20 YR (MIN)
Warranty rated life            3 YR (MIN)
Current rating                 34 А (IEC 60364-5-52 /
GOST R 50571-5-52)
Fire safety requirements:
1. Fire hazard category (cable marking) А
2. The toxicity index of combustion products > 40 g/m³
2. Smoke Density (minimum light transmission) > 60%
Resistance to external factors:
Climatic modification and placement category
HL/UHL 1 GOST 15150
By agreement with the customer, it is allowed to change the
climatic  modification and placement category depending on
the laying conditions
Resistance to alternating bending deformations, cycles
(movements), not less than
Operation requirements:
1. Place of operation:
Onshore technological complexes the cables in all respects,
be suitable for operation in conditions prevailing within a
typical petrochemical facility and the stated service
conditions where the atmosphere shall be regarded as
saliferous and corrosive, as commonly encountered in
installations in close proximity to the
2. Appointment:
The wires are intended for distribution of electric energy
in the electric installations at stationary laying in
lighting and power electric networks as well as for
installation of electrical equipment, machines, tools and
other machines, indoor electric settings
Compliance with regulatory requirements:
1. IEC 60227-3 / GOST IEC 60227-3 or GOST 31947
(Requirements for the construction, size and testing)
2. IEC 60332 - 3-22/  GOST IEC 60332-3-22 (flame spread test
on bunched cables)
3. EN 50305/GOST 12.1.044 (Checking the toxicity index of
combustion products)
4. IEC 61034-2/  GOST IEC 61034-2 (Smoke emission test)
5. The tests at low temperature shall be done in accordance
with IEC 60811-506 for cold impact and IEC 60811-504 for
cold bending or IEC 60811-505 for elongation at break when
the cable is not subjected to bending test.
The tests shall be carried out at a test temperature of (-45
+/- 2) °C for the cold bending and at (-40 +/- 2) °C for the
cold impact test.
Notes:
1. Any deviations from the stated requirements must be
communicated to the Customer and agreed.
2. Manufacturer shall list in his quotation the type tests
and routine tests to which his cables are Subjected
Abbreviations:
1. Cu - сopper
2. LSHF - extruded layer of halogen free low smoke
thermoplastic compound based on polymer compositions
Type tests:
Tests made before supplying, on a general commercial basis,
a type of cable covered by this standard, in order to
demonstrate satisfactory performance characteristics to meet
the intended application
Routine tests:
Tests made by the manufacturer on each manufactured length
of cable to check that each length meets the specified
requirements

Recommended for purchase in Russian Federation

VENDOR DOCUMENT REQUIREMENTS:
A01 Vendor Master Data Schedule (VMDS)
B07 Vendor's Declaration of Compliance
H18 Catalogue Data
K04 Factory Acceptance Test (FAT) Report
K38 CU TR Certificate , Declaration of Conformity for Low Voltage Equipment
K39 RF , CU TR fire Safety Certificate of Conformity
L04 Quality Management Accreditation eg ISO 9000 (including any manufacturing licenses held by Vendor, e.g. API, ASME etc.)
N01 Installation, Commissioning, Operating & Maintenance Manuals
P06 Preparation for Shipping with Recommended Handling, Storage & Preservation Procedures
CBL ELEC N-ARM FIRE,0.38/0.66KV,3X1.5MM²
Fire spec non armoured electrical cable

Flammability properties        FLAME RETANDANT
Voltage                        0.38/0.66 kV
Construction                   Cu/PVC/PVC
Mat, conductor wire            UNCOATED ANNEALED COPPER
Mat spec, insulation           PVC
Mat spec, outer sheath         PVC
Colour, outer sheath           BLACK
Identification, cores          BROWN(L), BLUE(L) +
                               GREEN/YELLOW(EARTH)
Number, cores                  3
Cross section, cores           1.5 mm²
Diameter, od, overall          7.4 TO 9.4 mm

Frequency, nominal             50 Hz
Shape                          CIRCULAR
Class                          5
Standard                       IEC 60228/GOST 22483
Resistance, conductor DC, max  13.3 ohm/km AT 20 °C
Reactance, approx              0.126 ohm/km AT 50 Hz
Current rating, short-circuit  0.54/0.24/0.17 kA
(0.1/0.5/1.0 s)
Temperature rating, conductor  70 °C (OPERATING)
160 °C (SHORT CIRCUIT)
Test voltage                   2000 Vac
Temperature range , ambient    -40 TO +40 °C
Relative humidity              98%  AT 35 °C
Installation temperature       -15 °C (WITHOUT PRE-HEATING)
Nominal tensile load           14.7 N
Weight, approximate            150 kgs/km
Service life                   10 YR (MIN)
Warranty rated life            2 YR (MIN)
Current rating                 18.5 А (IEC 60364-5-52 /
GOST R 50571-5-52)
Fire safety requirements:
1. Fire hazard category (cable marking) А
2. The toxicity index of combustion products > 40 g/m³
2. Smoke Density (minimum light transmission) > 50%
Resistance to external factors:
Climatic modification and placement category
U/UHL 4 GOST 15150
By agreement with the customer, it is allowed to change the
climatic  modification and placement category depending on
the laying conditions
Resistance to alternating bending deformations, cycles
(movements), not less than
Operation requirements:
1. Place of operation:
Onshore technological complexes the cables in all respects,
be suitable for operation in conditions prevailing within a
typical petrochemical facility and the stated service
conditions where the atmosphere shall be regarded as
saliferous and corrosive, as commonly encountered in
installations in close proximity to the
2. Appointment:
The wires are designed to connect electrical machines and
appliances for domestic and similar use to the electrical
network.
Compliance with regulatory requirements:
1. IEC 60227-5 or GOST7399 (Requirements for the
construction, size and testing)
2. IEC 60332 - 3-22/  GOST IEC 60332-3-22 (flame spread test
on bunched cables)
3. EN 50305/GOST 12.1.044 (Checking the toxicity index of
combustion products)
4. IEC 61034-2/  GOST IEC 61034-2 (Smoke emission test)
5. The tests at low temperature shall be done in accordance
with IEC 60811-506 for cold impact and IEC 60811-504 for
cold bending or IEC 60811-505 for elongation at break when
the cable is not subjected to bending test.
The tests shall be carried out at a test temperature of (-40
+/- 2) °C for the cold bending and at (-35 +/- 2) °C for the
cold impact test.
Notes:
1. Any deviations from the stated requirements must be
communicated to the Customer and agreed.
2. Manufacturer shall list in his quotation the type tests
and routine tests to which his cables are Subjected
Abbreviations:
1. Cu - сopper
2. PVC - polyvinyl chloride
Type tests:
Tests made before supplying, on a general commercial basis,
a type of cable covered by this standard, in order to
demonstrate satisfactory performance characteristics to meet
the intended application
Routine tests:
Tests made by the manufacturer on each manufactured length
of cable to check that each length meets the specified
requirements


Recommended for purchase in Russian Federation

VENDOR DOCUMENT REQUIREMENTS:
A01 Vendor Master Data Schedule (VMDS)
B07 Vendor's Declaration of Compliance
H18 Catalogue Data
K04 Factory Acceptance Test (FAT) Report
K38 CU TR Certificate , Declaration of Conformity for Low Voltage Equipment
K39 RF , CU TR fire Safety Certificate of Conformity
L04 Quality Management Accreditation eg ISO 9000 (including any manufacturing licenses held by Vendor, e.g. API, ASME etc.)
N01 Installation, Commissioning, Operating & Maintenance Manuals
P06 Preparation for Shipping with Recommended Handling, Storage & Preservation Procedures
CBL ELEC ARM FIRE,3CX4AWG,0.6/1KV,BLK
Cable, Electrical, Armoured, Fire spec

Voltage                        0.6/1 kV
Design spec                    IEEE 1580 AND UL 1309
Mat spec, insulation           IEEE 1580, TYPE P
                               UL 1309, X110
Mat spec, outer sheath         IEEE 1580 AND  UL 1309, TYPE N
Colour, outer sheath           BLACK
Number, cores                  3 C
Cross section, cores           4 AWG

Cable designation              TPNBS
CBL ELEC ARM FIRE,600/1000V,4PR,16AWG
Cable, Electrical, Armoured, Fire spec

Flammability properties        FLAME RETARDANT
Voltage                        600 / 1000 V
Design spec                    IEEE 1580 AND UL 1309
Mat spec, insulation           IEEE 1580, TYPE P
                               UL 1309, X110
Colour, outer sheath           BLACK
Number, cores                  4 PR
Cross section, cores           16 AWG

Cable, designation             TP(IS-OS)PNBS


Differences between an Armoured Cable and an Unarmoured Cable

AspectArmoured CableUnarmoured Cable
Level of ProtectionArmoured Cable has an additional level of protection made of metal, protecting it from physical damage, moisture, and other environmental factors.There is no external protective layer in unarmoured cable, which makes it more vulnerable to damage from external factors.
CostArmoured cables are more expensive due to the additional protective layer.Unarmoured cable doesn't have any kind of protective layer, which is why it is less expensive.
ApplicationsArmoured cables are suitable for use in hazardous environments, such as underground installations, areas with high moisture levels, and areas prone to mechanical damage.Unarmoured cables are suitable for less demanding applications, such as inside walls or other protected locations.
Underground InstallationArmoured Cables are ideal for direct burial and laying underground, protecting against environmental factors.Unarmoured cables are unsuitable for burial or use in other applications and installations.